所有样本集的95%LRV大于或等于4.8log
E.大肠杆菌: 观察到的LRV中位数=6.2 log
所有样本集的95%LRV大于或等于4.8log
本地病毒: 观察到的LRV中位数= 3.8 log
所有样本集的95%LRV大于或等于3.1 log
在十个运行1.5至7.5年的工厂中进行的全面性能采样程序显示,膜渗透性大肠菌群浓度始终较低,大大低于实际废水要求。
参考文献
Guibert,D.,Colling,A(2011)Direct membrane integrity testing:Impact of parameter selection on log removal valuecal culations Desal.,272(1-3),174-178
Guo,H.;Wyart,Y.;Perot,J.; Nauleau,F.;Moulin,P.(2010)Low-pressure membrane integrity tests for drinking water treatment:Areview.Water Res.,44(1),41-57
Hirani,Z.M.,DeCarolis,J.F.,Adham,S.S.,Jacangelo,J.G.Peak flux performance and microbial removal by selected membrane bioreactor systems(2010)Water Res.,44(8),2431-2440.
USEPA,MembraneFiltrationGuidanceManual.EPA815-R-06009,UnitedStates Environmental Protection Agency,WashingtonDC,2005
Zanetti,F.,DeLuca,G.,Sacchetti,R.Performance of a full-scale membrane bioreactor system intreating municipal wastewater for reuse purposes(2010)Biores.Techn.,101(10),3768-3771.
Zhang,K.,Farahbakhsh,K.Removal of native coliphages and coliform bacteria from municipal wastewater by various wastewater treatment processes:Implications to water reuse (2007)Water Res.,41(12),2816-2824.
孙晓航
中国水网金牌专栏作家
北控水务技术委员会委员、北控水务中部区运营总经理兼总工
编辑:徐冰冰
版权声明:
凡注明来源为“中国水网/中国固废网/中国大气网“的所有内容,包括但不限于文字、图表、音频视频等,版权均属E20环境平台所有,如有转载,请注明来源和作者。E20环境平台保留责任追究的权利。